IEC 60331 Electric or Optical Fibre Cables Circuit Integrity Burning Testing Equipment
Description:
The tester is suitable for test electric and optical fibre under the flame not less than 750¡æ, whether keep circuit integrity under fire conditions.
Standards:
GB/T19216 Test for electric or optical fibre cables under fire conditions---Circuit Integrity--Procedures and requirement for fire with shock--Cables of rated voltage up to and including 0.6/1KV
IEC60331 Tests for electric cables under fire conditions---Circuit Integrity--Procedures and requirement for fire with shock--Cables of rated voltage up to and including 0.6/1KV
Specifications:
1. Burner:Venturi mixer for the nozzle with a nominal length of 500mm width of 15mm belt type propane gas torch. The nozzle has three rows of staggered nominal diameters 1.32 mm, the center distance of 3.2 mm drilling;
2. Air flowmeter: 80L / min, propane flowmeter: 5L / min;
3. The burner control system is made of pressure regulator, piezoelectric igniter, flameout device, temperature control thermocouple, gas source (owned), control valve, ignition device, gas pipeline, flow meter, Venturi mixer , Sprayer, ball valve, air lines, air compressed bottles(owned);
4. Timer: 0 ~ 99.99s / m / h arbitrarily set;
5. Ignition device: for automatic ignition;
6. Temperature controller: temperature monitoring by the two parts, the temperature range: 0 ~ 1000 ¡æ arbitrarily set;
7. Test transformer: three sets 3000VA;
8. Test voltage: AC 1000V;
9. Test current: 3A.